Purpose:
Controls and alerts the high flammable and
toxic gases content in the work area
Application:
Boiler rooms (liquefied and natural gas),
industrial, administrative and residential
areas
Technical specifications:
|
SGS-901 |
SGS-902 |
Number
of channels |
2
|
2
|
Number
of programmable launches |
2
|
2 |
Type
of signal |
‘dry’
contact,
light, sound |
‘dry’ contact,
light, sound |
Launch values of alarm
-
for flammable gases, % LCLFP
-
for toxic gases, mg/m3 |
1st
limit 10 � 5
2nd limit
20 � 5
1st limit
1 MAC
2nd limit
5 MAC |
1st limit
10 � 5
2nd limit
40 � 5
1st limit
1 MAC
2nd limit
5 MAC
|
Explosion
protection |
none
|
1ExibIIC(B)T6(T4) |
Power
supply |
220 V, 50 Hz
|
220 V, 50 Hz |
Communication
channel |
4-20 mA |
4-20
mA |
Work range of
temperatures, C� |
From 0 to +50 |
From -20 to +50 |
The alarm
device consists of the control and alert
compartment and the probes with
electrochemical and thermocatalytic sensors
Detectable gases:
- toxic: CO, NO2, H2S, SO2, NH3, O2 and
others
- flammable: methane, propane, butane,
acetylene, ethanol, methanol,
acetone, hydrogen and others
There is a possibility to use probes as
separate alarm devices without the control
compartment
Advantages:
- works from 220 V outlet
- simple to install and use
- long life cycle
- small size
- high sensitivity
- digital output RS-485
|